KE300A Inverter Parameter Description
125
P8-36
Output current over limit value
Factory default
200.0%
Setting range
0.0% (No detection)
0.1% ~ 300.0% (motor rated current)
P8-37
Output current over limit detection delay time
Factory default
0.00s
Setting range
0.00s ~ 360.00s
When the output current is bigger than or over-limit detection point, lasts for longer than software over
current point detection delay time, DO terminal outputs ON signal.
Output current over
limit value
P8-36
Output current
Output current over
limit detection signal
Time (t)
Time (t)
Output current over
limit detection delay
time P8-37
Figure 6-21 Output current over limit function diagram
P8-38
Any arrival current 1
Factory default
100.0%
Setting range
0.0% ~ 300.0% (motor rated current)
P8-39
Any arrival current 1 amplitude
Factory default
0.0%
Setting range
0.0% ~ 300.0% (motor rated current)
P8-40
Any arrival current 2
Factory default
100.0%
Setting range
0.0% ~ 300.0% (motor rated current)
P8-41
Any arrival current 2 amplitude
Factory default
0.0%
Setting range
0.0% ~ 300.0% (motor rated current)
When the output current is in the range of positive or negative detection amplitude of setting any arrival
current, DO terminal outputs ON signal. KE300A series inverter provides two parameters of any arrival
current and detection amplitude.