KE300A Inverter Function Parameter List
73
Function
code
Name
Detailed instruction
Factory
default
Modify
Pd Group: Communication Parameters
Pd-00
Baud rate
0: 300BPS
1: 600BPS
2: 1200BPS
3: 2400BPS
4: 4800BPS
5: 9600BPS
6: 19200BPS
7: 38400BPS
5
○
Pd-01
Data format
0: No parity check (8-N-2)
1: Even parity check (8-E-1)
2: Odd parity check (8-O-1)
3: No parity check (8-N-1)
0
○
Pd-02
Local address
0 ~ 247, 0 is broadcast address
1
○
Pd-03
Response delay
0ms ~ 20ms
2
○
Pd-04
Communication
timeout time
0.0 (invalid)
0.1s ~ 60.0s
0.0
○
Pd-05
Communication
protocol selection
0: Non-standard MODBUS protocol
1: Standard MODBUS protocol
1
○
Pd-06
Communication selection
Units place: Current resolution
0: 0.01A
1: 0.1A
Tens place Writing selection
0: Reply
1: No reply
00
○
PE Group: Reserved Function
PE-00
Reserved
○
PP Group: Function Code Management
PP-00
User password
0 ~ 65535
0
○
PP-01
Parameter initialization
0: No action
1: Restore factory default, but not
including motor parameters
2: Clear the record
0
◎
PP-02
Function parameter group
display selection
Units place: U0 group display selection
0: No display
1: Display
Tens place: A0 group display selection
0: No display
1: Display
00
◎
PP-03
Reserved
●