KE300A Inverter Parameter Description
106
Setting
value
Function
Description
temperature can be checked via U0-34)
40
This running time arrival
This running time exceeds the time set by P8-53, the inverter
outputs ON signal.
P5-06
HDO function selection
Factory default
0
P5-07
AO1 output function selection
Factory default
0
P5-08
AO2 output function selection
Factory default
0
The frequency range of HDO output pulse is 0.01 kHz ~ P5-09 (HDO maximum output frequency), P5-09
can be set between 0.01 kHz ~ 100.00 kHz.
The output range of analog output (AO1 & AO2) is 0V ~ 10V or 4mA ~ 20mA.
The corresponding value range that it indicates is shown in the table below:
Setting value
Function
Range
0
Running frequency
0 ~ maximum output frequency
1
Setting frequency
0 ~ maximum output frequency
2
Output current
0 ~ 2 times motor rated current
3
Output torque
0 ~ 2 times motor rated torque
4
Output power
0 ~ 2 times rated power
5
Output voltage
0 ~ 1.2 times inverter rated voltage
6
HDI
0.01kHz ~ 100.00kHz
7
AI1
0V ~ 10V
8
AI2
0V ~ 10V (or 0 ~ 20mA)
9
Reserved
10
Length
0 ~ maximum setting length
11
Count value
0 ~ maximum count value
12
Communication
0.0% ~ 100.0%
13
Motor speed
0 ~ maximum output frequency corresponding speed
14
Output current
0.0A~1000.0A
15
Output voltage
0.0V~1000.0V
P5-09
HDO output maximum frequency
Factory default
50.00kHz
Setting range
0.01kHz ~ 100.00kHz
When HDO terminal is selected as pulse output, this code is used to set the maximum frequency of output
pulse.
P5-10
AO1 Zero-offset coefficient
Factory default
0.0%
Setting range
-100.0% ~ +100.0%