KE300A Inverter Function Parameter List
69
Function
code
Name
Detailed instruction
Factory
default
Modify
6: AI1+AI2
7: MAX (|AI1|, |AI2|)
8: MIN (|AI1|, |AI2|)
PA-03
PID action direction
0: Positive
1: Negative
0
○
PA-04
PID given feedback range
PA-01(PID given through keypad)~
1000.0
100.0
○
PA-05
Proportional gain Kp1
0.0 ~ 100.0
20.0
○
PA-06
Integration time Ti1
0.01s ~ 10.00s
2.00s
○
PA-07
Differential time Td1
0.000s ~ 10.000s
0.000s
○
PA-08
Cutoff frequency
of PID reverse
0.00 ~ P0-10 (maximum frequency)
0.00Hz
○
PA-09
PID deviation limit
0.0% ~ 100.0%
0.0%
○
PA-10
PID differential amplitude
0.00% ~ 100.00%
0.10%
○
PA-11
PID given filter time
0.00 ~ 650.00s
0.00s
○
PA-12
PID feedback filter time
0.00 ~ 60.00s
0.00s
○
PA-13
PID output filter time
0.00 ~ 60.00s
0.00s
○
PA-14
Sampling period
0.00
~
65535
2
○
PA-15
Proportional gain Kp2
0.0 ~ 100.0
20.0
○
PA-16
Integration time Ti2
0.01s ~ 10.00s
2.00s
○
PA-17
Differential time Td2
0.000s ~ 10.000s
0.000s
○
PA-18
PID parameter
switching condition
0: No switching
1: Switching via terminals
2: Automatic switching according to the
deviation
0
○
PA-19
PID parameter switching
deviation 1
0.0% ~ PA-20
20.0%
○
PA-20
PID parameter switching
deviation 2
PA-19 ~ 100.0%
80.0%
○
PA-21
PID initial value
0.0% ~ 00.0%
0.0%
○
PA-22
PID initial value holding
time
0.00 ~ 360.00s
0.00s
○
PA-23
Forward maximum value
between two output
deviation
0.00% ~ 100.00%
1.00%
○
PA-24
Reverse maximum value
between two output
deviation
0.00% ~ 100.00%
1.00%
○