Enabling Alarms
For each alarm type, there are two enabling options:
•
Alarm declaration (
ENABLE
).
•
Automatic dialout when the alarm occurs (
DIAL
).
If alarm declaration is enabled for a specific alarm type, you can independently
select whether Access-T will dial out to report the alarm. If alarm declaration is
disabled, dialout will not occur.
Note:
If the
DIAL
function is turned on for an enabled alarm
after an alarm condition arises, Access-T will immediately dial
out to report the alarm. Similarly, if an alarm is disabled after
an alarm condition has been reported, the
ALERT
indication will
be erased from the Title Bar.
To enable an alarm, perform the following steps:
1.
Select
ALARMS
from the Main Menu Line.
2.
Select
SETUP
.
3.
Alarms are monitored at different points in the system. Select the type
of alarm group:
DTE
,
LINE
,
AUX PORT
, or
CHASSIS
and press the
Enter
key.
4.
Scroll through the alarm option list until the desired alarm condition
appears.
5.
Press the
Enter
key.
6. Select the
ENABLE
option and press the
Enter
key.
7.
Select
YES
to enable the alarm condition; select
NO
to disable the
alarm condition.
8.
Press the
Esc
key to return to the previous menu.
9. Select the
DIAL
option and press the
Enter
key.
10.
Select
YES
to enable automatic alarm dialout for this alarm
condition; select
NO
to disable dialout. (This option has no effect
if
ENABLE = NO
.)
11.
Press the
Esc
key repeatedly to return to the Main Menu Line.
ACST-0351-005
Chapter 6
June 1996
Configuration Procedures