P08.29
Auto fault reset
interval
automatic fault reset, it is used to set the
number of automatic fault reset times. When
the number of continuous reset times
exceeds the value, the VFD reports a fault
and stops.
Auto fault reset interval: Time interval from
when a fault occurred to when automatic
fault reset takes effect.
After VFD starts, If no fault occurred within
600s after the VFD starts, the number of
automatic fault reset times is cleared.
setting range: 0
–10
setting range: 0.1
–3600.0s
1.0s
○
P08.30
Frequency
decrease ratio in
drop control
The output frequency of the VFD changes as
the load changes. The function code is
mainly used to balance the power when
several motors drive a same load.
Setting range: 0.00
–50.00Hz
0.00Hz
○
P08.31
Channel for
switching
between motor 1
and motor 2
0x00
–0x14
Ones place: Switchover channel
0: Terminal
1: Modbus communication
2:
PROFIBUS/CANopen/DeviceNet
communication
3: Ethernet communication
4: EtherCat/Profinet communication
Tens place: indicates whether to enable
switchover during running
0: Disable
1: Enable
0x00
◎
P08.32
FDT1 electrical
level detection
value
When the output frequency exceeds the
corresponding frequency of FDT electrical
level, the multifunction digital output terminal
continuously
outputs
the
signal
of
"Frequency level detection FDT". The signal
50.00Hz
○
P08.33
FDT1 lagging
detection value
5.0%
○