IPE300 series engineering VFD
Communication protocol
-293-
First, set the serial port to
COM1
. Then, set the baud rate consistently with
. The data bits,
check bits, and end bits must be set consistently with
. If the RTU mode is selected, you need
to select the hexadecimal form
Input HEX
. To set the software to automatically execute the CRC
function, you need to select
ModbusRTU
, select
CRC16 (MODBU SRTU)
, and set the start byte to
1
.
After the auto CRC check function is enabled, do not enter CRC information in commands. Otherwise,
command errors may occur due to repeated CRC check.
The commissioning command to set the VFD whose address is 03H to be forward running is as
follows:
Parameter
address
VFD
address
Write
command
CRC
Forward running
03
06
20 00
00 01
42 28
Note:
1. Set the address (
) of the VFD to 03.
2. Set "Channel of running commands" (
) to "Communication", and set "Communication
channel of running commands" (
) to the Modbus communication channel.
3. Click Send. If the line configuration and settings are correct, a response transmitted by the VFD
is received as follows:
Parameter
address
VFD
address
Write
command
CRC
Forward running
03
06
20 00
00 01
42 28
9.5 Common communication faults
Common communication faults include the following:
No response is returned.
The VFD returns an exception response.
Содержание IPE300 Series
Страница 1: ...IPE300 Series Engineering VFD...
Страница 3: ......
Страница 35: ...IPE300 series engineering VFD Installation guidance 24 Figure 4 12 660V 22 45kW Figure 4 13 660V 55 132kW...
Страница 383: ...6 6 0 0 1 0 0 8 1 2 202106 V1 0...