IPE300 series engineering VFD
Function parameter list
-149-
Function
code
Name
Description
Default Modify
P06.14
AO1 output
0: Running frequency
1: Set frequency
2: Ramp reference frequency
3: Rotational speed (10V corresponds to the
speed corresponding to the max. output
frequency)
4: Output current (10V corresponds to twice the
VFD rated current)
5: Output current (10V corresponds to twice the
motor rated current)
6: Output voltage (10V corresponds to 1.5 times
the inverter unit rated voltage)
7: Output power (10V corresponds to twice the
motor rated power)
8: Set torque (10V corresponds to twice the
motor rated torque)
9:
Output
torque
(Absolute
value,
10V
corresponds to twice the motor rated torque)
10: AI1 input
11: AI2 input
12: AI3 input
13: High-speed pulse HDIA input
14: Value 1 set through Modbus communication
15: Value 2 set through Modbus communication
16:
Value
1
set
through
PROFIBUS/CANopen/DeviceNet communication
17:
Value
2
set
through
PROFIBUS/CANopen/DeviceNet communication
18: Value 1 set through Ethernet communication
19: Value 2 set through Ethernet communication
20: High-speed pulse HDIB input
21: Value 1 set through EtherCAT/Profinet
communication
22:
Torque
current
(bipolar,
100%
corresponding to 10V)
23: Exciting current (100% corresponding to
10V)
24: Set frequency (bipolar)
25: Ramp reference frequency (bipolar)
0
○
P06.15
Reserved
0
○
P06.16
HDO high-speed
pulse output
0
○