IPE300 series engineering VFD
Function parameter list
-134-
Function
code
Name
Description
Default Modify
△
f=f
b
-n*p/60
Of which, f
b
is the rated frequency of the motor 2,
corresponding to function code
. n is the
rated
rotating
speed
of
the
motor
2,
corresponding to function code
. p is the
number of pole pairs of the motor. 100.0%
corresponds to the rated slip frequency
△
f of
motor 2.
Setting range: 0.0
–200.0%
P04.23
Low-frequency
oscillation control
factor of motor 2
In space voltage vector control mode, the motor,
especially
the
large-power
motor,
may
experience
current
oscillation
at
certain
frequencies, which may cause unstable motor
running, or even VFD overcurrent. You can adjust
the two function codes properly to eliminate such
phenomenon.
setting range: 0
–100
setting range: 0
–100
output frequency)
10
○
P04.24
High-frequency
oscillation control
factor of motor 2
10
○
P04.25
Oscillation
of motor 2
30.00H
z
○
P04.26
Energy-saving
run
0: Disable
1: Automatic energy-saving run
In light-load state, the motor can adjust the output
voltage automatically to achieve energy saving.
0
◎
P04.27
Voltage setting
channel
0: Keypad (The output voltage is determined by
1: AI1
2: AI2
3: AI3
4: HDIA
5: Multi-step speed running (The setting is
determined by group P10.)
6: PID
7: Modbus communication
8:
PROFIBUS/CANopen/DeviceNet
communication
9: Ethernet communication
0
○
Содержание IPE300 Series
Страница 1: ...IPE300 Series Engineering VFD...
Страница 3: ......
Страница 35: ...IPE300 series engineering VFD Installation guidance 24 Figure 4 12 660V 22 45kW Figure 4 13 660V 55 132kW...
Страница 383: ...6 6 0 0 1 0 0 8 1 2 202106 V1 0...