IPE300 series engineering VFD
Function parameter list
-177-
Function
code
Name
Description
Default
Modify
P11.12
Underload
pre-alarm
detection time
underload pre-alarm detection time (
setting range: 0
–3600.0s
1.0s
○
P11.13
Fault output
terminal action
upon fault
occurring
Used to set the action of fault output
terminals at undervoltage and fault reset.
0x00
–0x11
Ones place:
0: Act upon an undervoltage fault
1: Do not act upon an undervoltage fault
Tens place:
0: Act during automatic reset
1: Do not act during the automatic reset
period
0x00
○
P11.14
Speed deviation
detection value
0.0
–50.0%
Used to set the speed deviation detection
value.
10.0%
○
P11.15
Speed deviation
detection time
Used to set the speed deviation detection
time.
Note:
Speed deviation protection is invalid
when
=0.0.
Speed
Actual detection
value
Set detection
value
Time t
t1
t2
t2=P11.15
t1<t2, so the VFD continues running
dEu
Running
Fault output
Setting range: 0.0
–10.0s
1.0s
○
P11.16
Automatic
frequency-reduct
ion during
voltage drop
0
–1
0: Disable
1: Enable
0
○
P11.17
Proportional
coefficient of
voltage regulator
during
undervoltage
stall
This parameter is used to set the
proportional coefficient of the bus voltage
regulator during undervoltage stall.
Setting range: 0
–1000
100
○
P11.18
Proportional
This parameter is used to set the integral
40
○