IPE300 series engineering VFD
Basic operation guidelines
-89-
Function
code
Name
Description
Default
57: Motor overtemperature fault input
59: Switch to V/F control
60: Switch to FVC control
61: Switch PID polarities
62: Reserved
63: Enable servo
64: Limit on forward running
65: Limit on reverse running
66: Clear encoder counting
67: Increase pulses
68: Enable pulse superposition
69: Decrease pulses
70: Electronic gear selection
71: Switch to the master
72: Switch to the slave
73: Enable RO output 1
74: Enable RO output 2
75: Brake release command input
76: Brake feedback signal
77
–79: Reserved
Input terminal polarity
0x00
–0x3F
0x00
Digital input filter time
0.000
–1.000s
0.010s
Virtual terminal setting
0x00
–0x3F (0: disable, 1: enable)
BIT0: S1 virtual terminal
BIT1: S2 virtual terminal
BIT2: S3 virtual terminal
BIT3: S4 virtual terminal
BIT4: HDIA virtual terminal
BIT5: HDIB virtual terminal
0x00
Terminal control mode
0: Two-wire control mode 1
1: Two-wire control mode 2
2: Three-wire control mode 1
3: Three-wire control mode 2
0
S1 switch-on delay
0.000
–50.000s
0.000s
S1 switch-off delay
0.000
–50.000s
0.000s
S2 switch-on delay
0.000
–50.000s
0.000s
S2 switch-off delay
0.000
–50.000s
0.000s
S3 switch-on delay
0.000
–50.000s
0.000s
S3 switch-off delay
0.000
–50.000s
0.000s