IPE300 series engineering VFD
Function parameter list
-143-
Function
code
Name
Description
Default Modify
FWD
REV
COM
Sln
SB2
SB1
SB3
Sin
FWD
REV
Running
direction
ON
OFF→ON
ON
FWD run
OFF
FWD run
ON
ON
OFF→ON
REV run
OFF
REV run
ON→OFF
Decelerate
to stop
Sin: Three-wire control; FWD: Forward running;
REV: Reverse running
Note:
For two-wire controlled running mode,
when the FWD/REV terminal is valid, if the VFD
stops due to a stop command given by another
source, the VFD does not run again after the stop
command disappears even if the control terminal
FWD/REV is still valid. To make the VFD run, you
need to trigger FWD/REV again, for example,
PLC single-cycle stop, fixed-length stop, and
valid STOP/RST stop during terminal control.
P05.12
S1 switch-on
delay
Used to specify the delay time corresponding to
the
electrical
level
changes
when
the
programmable input terminals switch on or switch
off.
Si electrical level
Si valid
invalid
invalid
Switcn-on
delay
Switcn-off
delay
valid
Setting range: 0.000
–50.000s
0.000s
○
P05.13
S1 switch-off
delay
0.000s
○
P05.14
S2 switch-on
delay
0.000s
○
P05.15
S2 switch-off
delay
0.000s
○
P05.16
S3 switch-on
delay
0.000s
○