IPE300 series engineering VFD
Basic operation guidelines
-91-
Setting
Function
Description
5
VFD in fault
Output ON signal when VFD fault occurred
6
Frequency level
detection FDT1
Refer to the description for
7
Frequency level
detection FDT2
Refer to the description for
8
Frequency reached Refer to the description for
9
Running in zero speed
Output ON signal when the VFD output frequency and reference
frequency are both zero.
10
Upper limit frequency
reached
Output ON signal when the running frequency reaches upper
limit frequency
11
Lower limit frequency
reached
Output ON signal when the running frequency reached lower
limit frequency
12
Ready for running
Main circuit and control circuit powers are established, the
protection functions do not act; when the VFD is ready to run,
output ON signal.
13
Pre-exciting
Output ON signal during pre-exciting of the VFD
14
Overload pre-alarm
Output ON signal after the pre-alarm time elapsed based on the
pre-alarm threshold; see
15
Underload pre-alarm
Output ON signal after the pre-alarm time elapsed based on the
pre-alarm threshold. For details, see the descriptions for
16
Simple PLC stage
completed
When the present state of the simple PLC is completed, it
outputs a signal.
17
Simple PLC cycle
completed
When a single cycle of the simple PLC is completed, it outputs a
signal.
23
Modbus
communication virtual
terminal output
A signal is output based on the value set through Modbus
communication. When the value is 1, the ON signal is output;
when the value is 0, the OFF signal is output.
24
PROFIBUS/CANopen/
DeviceNet
communication virtual
terminal output
Output corresponding signal based on the set value of
PROFIBUS/CANopen; output ON signal when it is set to 1,
output OFF signal when it is set to 0
25
Ethernet
communication virtual
terminal output
A signal is output based on the value set through Ethernet
communication. When the value is 1, the ON signal is output;
when the value is 0, the OFF signal is output.
26
DC bus voltage
established
When the bus voltage is above the inverter undervoltage, the
output is valid.
27
Z pulse output
When the encoder Z pulse is reached, the output is valid, which
becomes invalid 10 seconds later.
Содержание IPE300 Series
Страница 1: ...IPE300 Series Engineering VFD...
Страница 3: ......
Страница 35: ...IPE300 series engineering VFD Installation guidance 24 Figure 4 12 660V 22 45kW Figure 4 13 660V 55 132kW...
Страница 383: ...6 6 0 0 1 0 0 8 1 2 202106 V1 0...