IPE300 series engineering VFD
Function parameter list
-182-
Function
code
Name
Description
Default
Modify
P12.28
Power display
calibration
coefficient of
motor 2
0.00
–3.00
1.00
○
P12.29
Parameter
display of motor
2
0: Display by motor type. In this mode, only
parameters related to the present motor type
are displayed.
1: Display all. In this mode, all the motor
parameters are displayed.
0
○
P12.30
System inertia of
motor 2
0
–30.000kgm
2
0.000
○
P12.31
–P
12.32
Reserved
0
–65535
0
○
P13 group
––SM control
Function
code
Name
Description
Default
Modify
P13.00
SM
injected-current
decrease ratio
Used to set the reduction rate of the input
reactive current. When the active current of
the synchronous motor increases to some
extent, the input reactive current can be
reduced to improve the power factor of the
motor.
Setting range: 0.0%
–100.0% (of the motor
rated current)
80.0%
○
P13.01
Detection mode
of initial pole
0: Disable
1: Pulse detection mode
2: Pulse detection mode
0
◎
P13.02 Injected current 1
Pull-in current is the pole position orientation
current; pull-in current 1 is valid within the
lower limit of pull-in current switch-over
frequency threshold. If you need to increase
the start torque, increase the value of this
function parameter properly.
Setting range: 0.0%
–100.0% (of the motor
rated current)
20.0%
○
P13.03 Injected current 2
Pull-in current is the pole position orientation
current; pull-in current 2 is valid within the
lower limit of pull-in current switch-over
frequency threshold.
10.0%
○
Содержание IPE300 Series
Страница 1: ...IPE300 Series Engineering VFD...
Страница 3: ......
Страница 35: ...IPE300 series engineering VFD Installation guidance 24 Figure 4 12 660V 22 45kW Figure 4 13 660V 55 132kW...
Страница 383: ...6 6 0 0 1 0 0 8 1 2 202106 V1 0...