Function parameter list
-129-
Function
code
Name
Description
Default Modify
P03.35
Control
optimization
setting
Ones place: Reserved
0: Reserved
1: Reserved
Tens place: Reserved
0: Reserved
1: Reserved
Hundreds place: indicates whether to enable
speed-loop integral separation
0: Disable
1: Enable
Thousands place: Reserved
0: Reserved
1: Reserved
Range: 0x0000
–0x1111
0x0000
○
P03.36
Speed-loop
differential gain
0.00
–10.00s
0.00s
○
P03.37
High-frequency
current-loop
proportional
coefficient
In
the
closed-loop
vector
control
mode
=3), when the frequency is lower than the
current-loop high-frequency switching threshold
), the current-loop PI parameters are
and
; and when the frequency is
higher than the current-loop high-frequency
switching
threshold,
the
current-loop
PI
parameters are
setting range: 0
–20000
setting range: 0
–20000
–100.0% (of the max.
frequency)
1000
○
P03.38
High-frequency
current-loop
integral
coefficient
1000
○
P03.39
Current-loop
high-frequency
switching
threshold
100.0%
○
P03.40
Enabling inertia
compensation
0: Disable
1: Enable
0
○
P03.41
Upper limit of
inertia
compensation
torque
The max. inertia compensation torque is limited
to prevent inertia compensation torque from
being too large.
Setting range: 0.0
–150.0% (of the motor rated
torque)
10.0%
○
P03.42
Inertia
compensation
filter times
Filter times of inertia compensation torque, used
to smooth inertia compensation torque.
Setting range: 0
–10
7
○