IPE300 series engineering VFD
Function parameter list
-243-
Function
code
Name
Description
Default
Modify
4: PTC input (If AIAO is used, set P93.23=2; if
S terminal is used, set P93.23=1)
Note:
Switch the output of AO1 to current, and
connect one end of the temperature resistor to
AI1 and AO1, and the other end to GND
.
Note:
When 1
–4 is selected, P06.14 is
defaulted to “32: Source output at constant
current”.
P93.21
AIAO detected
temperature
-20.0
–200.0°C
0
●
P93.22
AIAO detected
motor
overtemperature
protection
threshold
0.0
–200.0°C
110.0
○
P93.23
PTC motor
protection mode
0: No detection
1: S terminal input protection
2: AIAO detection protection
0
○
P93.24
AO output
current setting
when PTC is
detected by
AIAO
0.000
–20.000mA
4.000
○
P93.25
Overtemp
protection
resistance point
when PTC is
detected by
AIAO
0
–60000Ω
750
○
P93.26
Actual resistance
value when PTC
is detected by
AIAO
0
–60000Ω
0
●
P93.27
Motor overtemp
protection
selection
0
–1
0: Action in P93.29 is conducted when: the
detected temperature exceeds the overtemp
threshold; the detected resistance exceeds the
overtemp protection resistance; PTC selected
by terminal function is enabled; or the
overtemp fault A-OHt is reported.
0
○