IPE300 series engineering VFD
Function parameter list
-222-
Function
code
Name
Description
Default Modify
P25.19
S8 switch-off
delay
0.000s
○
P25.20
S9 switch-on
delay
0.000s
○
P25.21
S9 switch-off
delay
0.000s
○
P25.22
S10 switch-on
delay
0.000s
○
P25.23
S10 switch-off
delay
0.000s
○
P25.24
AI3 lower limit Used to define the relationship between the
analog input voltage and its corresponding
setting. When the analog input voltage exceeds
the range from the upper limit to the lower limit,
the upper limit or lower limit is used.
When the analog input is current input,
0mA
–20mA current corresponds to 0V–10V
voltage.
In different applications, 100.0% of the analog
setting corresponds to different nominal values.
See the descriptions of each application section
for details.
The following figure illustrates the cases of
several settings:
-100%
100%
Corresponding
setting
AI
10V
20mA
0
AI3/AI4
Input filter time: to adjust the sensitivity of analog
input. Increasing the value properly can enhance
analog input anti-interference but may reduce the
sensitivity of analog input.
Note:
AI3 and AI4 can support 0
–10V/0–20mA
input. When AI3 and AI4 select 0
–20mA input,
the corresponding voltage of 20mA is 10V.
0.00V
○
P25.25
Corresponding
setting of AI3
lower limit
0.0%
○
P25.26
AI3 upper limit
10.00V
○
P25.27
Corresponding
setting of AI3
upper limit
100.0%
○
P25.28
AI3 input filter
time
0.030s
○
P25.29
AI4 lower limit
0.00V
○
P25.30
Corresponding
setting of AI4
lower limit
0.0%
○
P25.31
AI4 upper limit
10.00V
○
P25.32
Corresponding
setting of AI4
upper limit
100.0%
○
P25.33
AI4 input filter
time
0.030s
○