IPE300 series engineering VFD
Basic operation guidelines
-77-
Function
code
Name
Description
Default
Tens place: HDIB input type
0: HDIB is high-speed pulse input
1: HDIB is digital input
AI1 lower limit
0.00V
0.00V
Corresponding setting of AI1
lower limit
-300.0%
–300.0%
0.0%
AI1 upper limit
–10.00V
10.00V
Corresponding setting of AI1
upper limit
-300.0%
–300.0%
100.0%
AI1 input filter time
0.000s
–10.000s
0.100s
AI2 lower limit
-10.00V
-10.00V
Corresponding setting of AI2
lower limit
-300.0%
–300.0%
-100.0%
AI2 middle value 1
0.00V
Corresponding setting of AI2
middle value 1
-100.0%
–100.0%
0.0%
AI2 middle value 2
0.00V
Corresponding setting of AI2
middle value 2
-300.0%
–300.0%
0.0%
AI2 upper limit
–10.00V
10.00V
Corresponding setting of AI2
upper limit
-300.0%
–300.0%
100.0%
AI2 input filter time
0.000s
–10.000s
0.100s
HDIA high-speed pulse input
function selection
0: Input set through frequency
1: Reserved
2: Input set through encoder, used
together with HDIB
0
HDIA lower limit frequency 0.000 kHz
0.000kHz
Corresponding setting of
HDIA lower limit frequency
-300.0%
–300.0%
0.0%
HDIA upper limit frequency
–50.000kHz
50.000kHz
Corresponding setting of
HDIA upper limit frequency
-300.0%
–300.0%
100.0%
HDIA frequency input filter
time
0.000s
–10.000s
0.030s
HDIB high-speed pulse input
function selection
0: Input set through frequency
1: Reserved
0