IPE300 series engineering VFD
Function parameter list
-183-
Function
code
Name
Description
Default
Modify
Setting range: 0.0%
–100.0% (of the motor
rated current)
P13.04
Source-current
switchover
frequency
0.00Hz
(Max. output frequency)
10.00Hz
○
P13.05
Reserved
200Hz
–1000Hz
500Hz
◎
P13.06
High-frequency
superposition
voltage
Used to set the pulse current threshold when
the initial magnetic pole position is detected
in the pulse mode, The value is a percentage
in relative to the rated current of the motor.
Setting range: 0.0
–300.0% (of the motor
rated voltage)
100.0%
◎
P13.07
Reserved
0.0
–400.0
0.0
○
P13.08
Control
parameter 1
0
–0xFFFF
0
○
P13.09
Control
parameter 2
Used to set the frequency threshold for
enabling the counter-electromotive force
phase-locked loop in SVC 0. When the
running frequency is lower than the value of
the function code, the phase-locked loop is
disabled; and when the running frequency is
higher than that, the phase-locked loop is
enabled.
Setting range: 0
–655.35
2.00
○
P13.10
Reserved
0.0
–359.9
0.0
○
P13.11
Maladjustment
detection time
Used to adjust the responsiveness of
anti-maladjustment function. If the load
inertia is large, increase the value of this
parameter
properly,
however,
the
responsiveness may slow down accordingly.
Setting range: 0.0
–10.0s
0.5s
○
P13.12
High-frequency
compensation
coefficient of SM
Valid when the motor speed exceeds the
rated speed. If oscillation occurred to the
motor, adjust this parameter properly.
Setting range: 0.0
–100.0%
0.0%
○
P13.13
High-frequency
current-loop
0
–300.0%
20.0%
◎