IPE300 series engineering VFD
Function parameter list
-170-
Function
code
Name
Description
Default
Modify
buffering is invalid.
1: A+B frequency. Acceleration/ deceleration
of main reference A frequency source
buffering
is
valid.
The
acceleration/deceleration is determined by
(acceleration time 4).
P09.14
Low frequency
proportional gain
(Kp)
0.00
–100.0
Low-frequency switching point: 5.00Hz,
high-frequency switching point: 10.00Hz
parameter), and the middle is the linear
interpolation between these two points.
1.00
○
P09.15
ACC/DEC time
of PID command
0.0
–1000.0s
0.0s
○
P09.16
PID output filter
time
0.000
–10.000s
0.000s
○
P09.17
Reserved
○
P09.18
Low frequency
integral time
Same as the description for
Setting range: 0.00
–10.00s
0.90s
○
P09.19
Low frequency
differential time
Same as the description for
Setting range: 0.00
–10.00s
0.00s
○
P09.20
Low frequency
point for PID
parameter
switching
setting range: 0.00
5.00Hz
○
P09.21
High frequency
point for PID
parameter
switching
10.00Hz
○
P09.22
–P
09.28
Reserved
0
–65536
0
○
P10 group
––Simple PLC and multi-step speed control
Function
code
Name
Description
Default
Modify
P10.00
Simple PLC
mode
0: Stop after running once. The VFD stops
automatically after running for one cycle, and it
can be started only after receiving the running
command.
0
○