IPE300 series engineering VFD
Function parameter list
-179-
Function
code
Name
Description
Default
Modify
P11.25
Enable VFD
overload integral
0: Disable
1: Enable
When this parameter is set to 0, the overload
timing value is reset to zero after the VFD is
stopped. In this case, the determination of
VFD overload takes more time, and therefore
the effective protection over the VFD is
weakened.
When this parameter is set to 1, the overload
timing value is not reset, and the overload
timing value is accumulative. In this case, the
determination of VFD overload takes less
time, and therefore the protection over the
VFD can be performed more quickly.
0
◎
P11.26
Reserved
0
–65536
0
○
P11.27
VF oscillation
control method
0x00
–0x11
Ones place:
0: Method 1
1: Method 2
Tens place:
0: Reserved
1: Reserved
0x00
◎
P12 group
––Parameters of motor 2
Function
code
Name
Description
Default
Modify
P12.00
Type of motor 2
0: Asynchronous motor (AM)
1: Synchronous motor (SM)
0
◎
P12.01
Rated power of
AM 2
0.1
–3000.0kW
Model
depended
◎
P12.02
Rated frequency
of AM 2
0.01Hz
(Max. frequency)
50.00Hz
◎
P12.03
Rated speed of
AM 2
1
–36000rpm
Model
depended
◎
P12.04
Rated voltage of
AM 2
0
–1200V
Model
depended
◎
P12.05
Rated current of
AM 2
0.8
–6000.0A
Model
depended
◎