Recommended Checks
For machines in low ambient conditions, offer the
customer the Low Ambient Kit. Search in Passport
for low ambient kits or contact Parts ID.
Ensure 2ATT is reading more than 35°F. Check for
loose/broken sensor.
For machines with low ambient kits ensure the heat
trace option is connected and the thermostat is set
no less than 50°F.
For more info, see Tech Note 7998.
High Inter Stage Pressure
Xe Software Logic for R & RS 2 stage units:
This will occur if the compressor is running and the
inter stage pressure (2APT) is greater than 75 psi (5.17
Bar). This trip will only occur in 2-stage compressors.
Recommended Checks
Is 2APT reading 0 psi when the machine is not
running? Calibrate sensor/check connection.