54
1ATT
– Package Inlet Temperature Sensor
Mounted at the inlet air ducting of the package, 1ATT
monitors the temperature of the incoming air to the
package. 1ATT has a range between -10°F (-23.33°C)
and 250°F (121.1°C).
The output voltage is 0.5 volts DC at 0°F to
4.5V DC at 246°F (118.9°C).
2ATT
– Air End Discharge Temperature Sensor
The controller uses 2ATT to monitor the temperature of
the air/coolant mixture as it leaves the Air End
discharge port. 2ATT has a range between -10°F (-
23.3°C) and 250°F (121.1°C).
The output voltage is 0.5 volts DC at 0°F to
4.5V DC at 246°F (118.9°C). The controller shows a
High Air End Discharge warning at 221°F (105°C). The
High Air End Discharge shutdown occurs at 228°F
(108.9°C). The alarm can be reset when 2ATT reads
below 217°F (102.8°C).
2CTT
‐
Injected Coolant Temperature
Mounted at the coolant filter discharge, 2CTT monitors
the temperature of the coolant being injected into the
Содержание Xe-145M
Страница 1: ...Control Systems Xe 90M 145M R RS Series Fixed Speed Technician s Pocket Guide...
Страница 13: ...12 R Series P1 Triac...
Страница 14: ...13 RS Series P1 Triac 115VAC...
Страница 41: ...40 Test on blower speed signal Tech Tube 10968 Machines with Low Ambient option installed...
Страница 54: ...53 5DTT and 6DTT option...
Страница 111: ...110 Triac Test 1...
Страница 112: ...111 Triac Test 2...
Страница 113: ...112 Triac Test 3...
Страница 114: ...113 Triac Test 4...
Страница 115: ...114 Triac Test 5...
Страница 116: ...115 Triac Test 6...