104
Ensure sump and package discharge sensors are
reading correctly with machine off. Check
sensor/reconnect sensors. Check ground.
Check for inlet filter assembly properly seating on
the inlet valve. Check for dirt and debris. Take oil
sample.
Blower Fault
Xe Software Logic for R & RS machines:
A:
Will occur if the Blower Control Type set point is set
to Variable Speed and the Fan Motor Overload digital
input opens for a period of 3 seconds.
The number of Blower Fault event occurrences may be
recorded in controller memory. This counter shall only
be available via Modbus and Field Service Tool and
shall be resettable via the FST.
The Xe controller ONLY shows the general alarm from
the blower drive.
To check a Blower Drive alarm a HIM or LCP device
needs to be connected to the Blower Drive to read the
specific alarm code/number.