Ensure the sensors 5CPT and 6CPT are reading 0
psi (0 Bar) when the machine is not running.
How many hours are on the coolant filter?
Compare to with the machine PM table for
reference.
Check inside the coolant filter for metal debris, or
foreign material.
Check piping and coolant filter housing for
obstruction.
If the sensors are fluctuating when the machine is
stopped, the wiring is not connected properly or the
wiring is touching an AC source. This causes
electrical noise in the DC signals.
Sensor Failure
Xe Software Logic for R & RS machines:
W & A:
This will occur whenever a temperature or
pressure sensor is missing, broken, or not connected
properly.
Recommended Checks