If this warning is reset while the conditions for running
the dryer exist, the dryer can restart. However, this
switch is a locking switch. The switch must be reset
before the dryer can run. Resetting the warning on the
display does not reset the switch.
Recommended Checks
High ambient temperature (if air cooled).
Dirty condenser (if water cooled).
High inlet air temperature.
High airflow rate.
Condenser fan operation.
Refrigerant charge.
Defective pressure sensor.
Condenser Temperature High
Xe Software Logic for R & RS machines:
This will occur if the condenser sensor has a value
above high temperature threshold while the dryer is
running, on compressors with the integrated dryer. This
is not a dryer fault. If this happens, the compressor and