106
sensor reads a value greater than 125°F (51.7°C)
(High Ambient OFF) or 135°F (57.2°C) (High Ambient
ON).
Recommended Checks
Compare 1ATT thermistor sensor to resistance
chart.
Is the ambient temp higher than 125°F?
Is the package exhaust air recirculating back to the
compressor inlet? Improve airflow to package.
Check connection of the sensor according to
Electrical Schematic. Is it in the right P6 terminal?
Control Power Loss
Xe Software Logic for R & RS machines:
Will occur if Control Power Loss is enabled,
Emergency Stop input is closed and the auxiliary 2
digital input closes for a time period of 0.5 seconds.
This will occur if the compressor should be running and
the AC input voltage, as read from the VSD, falls below
100 VAC. There is a delay of 2 seconds on this trip in