59
P9 RS485 Communication (COM1
‐
4)
In addition to USB and Ethernet communication, the Xe
has four RS-485 serial ports located at terminal plug
strip P9.
COM1
Airbus (RS485-1
Network)
P9-3 = L1 (+)
P9-4 = L2 (-)
COM2
Modbus
P9-1 = L1 (+)
P9-2 = L2 (-)
COM3
VSD (Nirvana
Only)
P9-7 = L1 (+)
P9-8 = L2 (-)
COM4
- Not used