61
P10
– 24VDC Power Supply
12-24VDC power required for controller logic, display,
analog and digital signals.
P10-2= Negative
P10-1= Positive
*Supply Input P10 = 10.9-26.4 VDC at 0.45 Amps
Electrical Schematic R & RS-Series
*
Both machines require an external DC voltage source
to power the controller. Ensure MCB5 circuit breaker is
closed/operational.