Air End. 2ATT has a range between -10°F (-23.3°C)
and 250°F (121.1°C).
The output voltage is 0.5 volts DC at 0°F (-17.8°C) to
4.5V DC at 246°F (118.9°C).
3CTT Coolant Cooler
‐
Out Temperature Sensor
(Option)
Mounted to the discharge of the coolant cooler (cold
side), 3CTT monitors the temperature of the coolant at
the cooler output.
3CTT has a range between -10°F (-23.3°C) and 250°F
(121.1°C). The output voltage is 0.5 volts DC at 0°F
(-17.8°C) to 4.5V DC at 246°F (118.9°C).
4ATT Package Discharge Temperature Sensor
Mounted at the package discharge, near the moisture
separator, 4ATT monitors the temperature of
compressed air downstream of the compressor’s
aftercooler.
This sensor is for information only and has no Warning
or Alarm feature. If the sensor is removed, the
controller shows the message “sensor failure” without
shutting down the compressor. This is informational
only.