Recommended Checks
For Dryer/TAS units, ensure the inline filters are
clean.
If piping is installed, bypass the dryer and re-test
Check the sequencer such as X8i is programmed
correctly. See Tech Note ID 11293.
Install a manual pressure gauge. Is the pressure
sensor reading accurately?
If the sensor is installed before or after a dryer,
could it be freezing?
Is the sensor able to calibrate to 0 PSIG (0 Bar)
when the system pressure is bled down?
Condensate Drain Error
Xe Software Logic for R & RS machines:
This will occur if the compressor is running, the
package discharge pressure is over 50 psi (0 Bar), and
the condensate drain error contact closes for at least
240 seconds. This warning will be ignored for 4.5
minutes after starting.