![Ingersoll-Rand Xe-145M Скачать руководство пользователя страница 29](http://html1.mh-extra.com/html/ingersoll-rand/xe-145m/xe-145m_pocket-manual_2059339029.webp)
28
ES-2) that open when the red E-
Stop button is pressed. Refer to the
electrical schematics for the correct
terminal location. ES-1 contact (red
wires) is located just after MCB3 in
the 115 VAC circuit and connects
to terminal P1-1
ES-2 contact (blue wires) is located in the 24 VDC logic
circuit at P3 7-8 for R-Series or P3 1-2 for RS-Series.
These contacts act in parallel to ensure power is
removed from the starter coils, solenoids, and
controller logic to cause the compressor to stop
immediately. The E-Stop will remain in the open
position until manually reset by pulling the red E-Stop
button forward.
Содержание Xe-145M
Страница 1: ...Control Systems Xe 90M 145M R RS Series Fixed Speed Technician s Pocket Guide...
Страница 13: ...12 R Series P1 Triac...
Страница 14: ...13 RS Series P1 Triac 115VAC...
Страница 41: ...40 Test on blower speed signal Tech Tube 10968 Machines with Low Ambient option installed...
Страница 54: ...53 5DTT and 6DTT option...
Страница 111: ...110 Triac Test 1...
Страница 112: ...111 Triac Test 2...
Страница 113: ...112 Triac Test 3...
Страница 114: ...113 Triac Test 4...
Страница 115: ...114 Triac Test 5...
Страница 116: ...115 Triac Test 6...