71
Recommended Checks
Check device or component connected to P3
terminal “AW1” in the Electrical Schematic of the
machine. The connection is normally open, so
whatever is connected issuing the warning must be
closed. Ask customer what is connected to the
terminal AW1 to troubleshoot the warning.
Auxiliary 2
Xe Software Logic for R & RS machines:
W:
This will occur if auxiliary input 2 closes. The
contact must be closed for at least 3 seconds before
the warning will occur.
This will occur if Control Power Loss is disabled and
auxiliary input 2 closes.
Recommended Checks
Check device or component connected to P3
terminal “AW2” in the Electrical Schematic of the
machine. The connection is normally open, so
whatever is connected issuing the warning must be