Recommended Checks
The condensate drain has a normally open switch
that receives 24 VDC from the controller. If the
condensate drain tries to release the condensate
water and the piping is clogged/dirty, the normally
open switch closes to allow the controller to see the
fault.
The 120 VAC power of the condensate drain only
energizes the drain to release the condensate
water.
Is the drain or piping dirty? A clogged pipe
won’t
allow the drain to discharge, causing an error in the
condensate drain.
The drain is 120 VAC, so it can be bench tested.
Freeze Warning
Xe Software Logic for R & RS machines:
This will occur if the evaporator sensor has a value of
687 (about 0.5 C) or below (low temp) while the dryer
is running, on compressors with the integrated dryer.
This is a dryer fault. If this happens, the compressor
will continue to run, but the dryer will stop. The