Recommended Checks
Add factory pass code to reset the alarm in factory
settings.
Select service warnings according to customer
needs/options installed. (High dust filter or EL
Coolant)
Communication Failure
Xe Software Logic for R & RS machines:
W:
This will occur if the compressor is the lead
compressor in integral sequencing and is unable to
communicate with another compressor.
Recommended Checks
Be sure ISC is only enabled on the Master.
Master should have Airbus Address of 1.
Be sure the comm cable is only grounded at the
Master.
Be sure all controllers have the latest software.
Be sure COMM Control is enabled on all
controllers.