cables of the remote stop means a good closed
circuit. A 24 VDC across the remote stop in P3
terminal shows an open circuit. Fix E-stop
switch.
Check quick connect plug
If the remote stop box in the status menu of the
controller is not selected, the controller is not
receiving the signal from the remote stop switch.
Check switch
Remote Start Failure
Xe Software Logic for R & RS machines:
Will occur if the remote start/stop option is enabled, the
compressor is started by the remote start button, and
the button stays closed for 7 seconds after the
compressor starts. The remote start switch is a
momentary switch (Only holds the connection closed
when it is manually pressed by the user)
Recommended Checks