42
directly proportional to pressure and follows a linear
path throughout its range.
The output signal is processed by an analog to digital
converter within the controller. Depending on the
voltage level, the controller may change the pressure
reading displayed, load/unload the compressor, or
possibly shut the compressor down.
If a pressure sensor is replaced, it is important to
calibrate the new sensor. Calibration allows the
controller to read the sensor’s output signal with the
diaphragm in a totally relaxed state and then correct for
any minor deviations from 0.5 VDC. Calibration
directions are included in the Operator’s Manual. There
are no adjustments to the pressure sensors
themselves.