Error Messages
HYDAC Filtertechnik GmbH
en
Page 81
BeWa CS1000 3247149l en.doc
2006-10-13
12.3.2 Analog signal for HDA 5500
12.3.2.1 HDA Status Signal 5 Table
The current or voltage of the output signal (5) is dependent on the status of the CS 1000 as shown in
the table below:
Current I
Status
Voltage U
I = 5.0 mA
The CS is functioning correctly
U = 2.5 V
I = 6.0 mA
Device error / CS not ready
U = 3.0 V
I = 7.0 mA
Flow too low (Flow 2 Low)
U = 3.5 V
I = 8.0 mA
Flow too high (Flow 2 high)
U = 4.0 V
I = 9.0 mA
No measured value (Flow undefined)
U = 4.5 V
If the status signal is
≥
6.0 mA or
≥
3.0 V, signals 1 to 4 are outputted with 20 mA or 10 V. Example:
I (mA)
U (V)
t (s)
4
2
6
3
9
4,5
10,0
7
5
3,5
2,5
8
4
20
2 2 2 2 2 2 2 2 2 2 2
2 2 2 2 2 2 2 2 2 2 2
30
1
1
0
2
2
3
3
4
4
5
5
0