12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
391
12
Alarm code
73
Mixing Overheating Limit Protection for mixed circuit (Only if Circuit 2 is enabled)
•
The alarm code is displayed on the LCD User interface.
•
The alarm code is displayed on the seven segments of the indoor unit PCB.
•
This alarm code is displayed when temperature of circuit 2 (mixed circuit) is 5ºC more than maximum water outlet
installer configuration for circuit 2.
Yes
Check that the contactors of the electrical heater
is not short circuited
No
Is the water outlet
circuit 2 (THMwo2)
temperature > Maximum
water outlet circuit 2
tempe5?
Faulty PCB1 (Check PCB)
Contact your local dealer
Check that the outlet water circuit 2 temperatures
is giving the correct reading
Check mixing station (water pump, mixing valve
position)
Contact your local dealer
1
2
3
4
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......