12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
401
12
Cause of inverter stoppage (11)
Cause of indoor unit stoppage (20)
Indication
Contents
1
IPM, ISPM, dipIPM error
2
Instantaneous over current
3
Inverter fin thermistor protection activation
4
Electronic thermal activation
5
Inverter voltage decrease
6
Over voltage
7
Abnormal transmission
8
Abnormal current detection
9
Instantaneous power failure detection
11
Reset of micro-computer for inverter
12
Earth fault detection from compressor
13
Open phase detection
14
Inverter malfunction
15
Inverter malfunction
16
Inverter malfunction
17
Transmission error
18
Abnormal current detection
19
Abnormal protective device
N O T E
To finish checking: press the PSW2 switch for
more than 3 seconds
Indication
Contents
00
Operation OFF, Power OFF
01
Thermo-OFF
02
Alarm
03
Freeze protection overheating protection
05
Instantaneous power failure at outdoor unit
06
Instantaneous power failure at indoor unit
07
Stoppage of cooling operation due to low outdoor air
temperature
Stoppage of heating operation due to high outdoor air
temperature
10
Demand thermo OFF
13
Retry for Pd increase prevention
15
Vacuum/discharge gas temperature increase retry
16
Retry due to discharge gas SUPERHEAT decrease
17
IPM error retry, instantaneous over current of inverter
retry, electronic thermal activation of inverter retry, abnor-
mal current sensor of inverter retry
18
Retry due to inverter voltage decrease
Retry due to
Inverter Over
voltage
19
Other retry
20
Different operation mode between indoor/outdoor units
(Only for individual twin/triple/quad types)
21
Forced thermo-OFF
(Only for simultaneous twin/triple/quad types)
22
Forced thermo-OFF
(During compressor pre-heating)
24
Thermo-OFF during energy saving operation mode
Cancelation of Forced Thermo OFF
Turn ON the power source and wait for more than 30 seconds. Then press PSW1 and PSW3 simultaneously for more
than 3 seconds.
Forced thermo-OFF (indoor unit error code 22) will be cancelled.
However, this function may damage the compressor, use only on inevitable occasion.
In case of using the remote control switch (PC-P1HE), the cancellation is also available with it.
When “operation is limited” indication flashes on the remote control LCD, press FAN SPEED and LOUVER switches
simultaneously for more than 3 seconds.
“Operation is limited” indication is disappeared and operation is available.
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......