5 Control system
SMGB0070 rev. 1 - 08/2011
148
Boiler minimum and maximum times
Boiler can only be stopped after minimum ON time has passed (6-004).
Boiler can only be started after minimum OFF time has passed (6-005).
1
0
1
0
6-006
1
0
6-004
6-005
Heat Demand by
Thermostat
Boiler demand
Boiler output
Request
No request
Request
No request
OFF
ON
Time
User Variables:
CODE
REF
Description
Default Value
Range
Steps
Units
6-004
Bon
Boiler minimum ON time
2 min
1 ~ 30
1
min
6-005
Boff
Boiler minimum OFF time
5 min
1 ~ 30
1
min
N O T E
Maximum water temperature of the installer have priority against Boiler minimum ON Time.
Emergency mode
When user allows emergency mode (DSW4-4 ON), boiler may operate in said mode.
In the case of Boiler combination, Boiler has priority.
N O T E
For more information refer to
Optional functions
chapter.
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......