3 Piping work and
refrigerant charge
SMGB0070 rev.1 - 08/2011
65
3
• Dimensions of the flared pipe
Units: mm (inch)
Nominal
diameter
External
diameter
A
Ø +0/-0.4
(1/4)
6.35
9.1
(3/8)
9.53
13.2
(1/2)
12.7
16.6
(5/8)
15.88
19.7
• Thickness of the copper pipes
Units: mm (inch)
Nominal
diameter
External
diameter
Thickness
(1/4)
6.35
0.80
(3/8)
9.53
0.80
(1/2)
12.7
0.80
(5/8)
15.88
1.00
• Dimensions of the flare nut
Units: mm (inch)
Nominal
diameter
External
diameter
B
(1/4)
6.35
17
(3/8)
9.53
22
(1/2)
12.7
26
(5/8)
15.88
29
•
Flare nuts tightening torque
Always use two wrenches or fix spanners when tightening the Flare Nuts on the refrigerent pipes.
If any failure occurs during this process the result could be pipe damage or refrigerant leak.
Unit: N.m
Pipe size
Tightening torque
Ø 6.35 mm
20
Ø 9.53 mm
40
Ø 12.7 mm
60
Ø 15.88 mm
80
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......