12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
346
Alarm code
07
Decrease of Discharge Gas Superheat
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
•
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section. The unit
number and the alarm code are displayed on the display of the outdoor unit PCB.
This alarm code is indicated as follows:
-
The temperature on the top of the compressor is less than the target and also the I.U. expansion valve opening
is under 300pls at cooling operation for 30 minutes.
-
The temperature on the top of compressor is less than the target and also the O.U. expansion valve opening is
under 70 pls at heating operation for 30 minutes.
-
The compressor is stopped and then the retry operation is performed after 30 minutes.
No
Faulty thermistor
Yes
Yes
Heating
No
Yes
Is the thermistor
on top of compressor
normal?
Install it correctly
Is the thermistor
installed correctly on
the compressor?
Heating operation
Is it at cooling or
heating mode when
the alarm has occurred?
Cooling
Cooling operation
Yes
Yes
Check the I.U. expansion valve opening and the
temperature on the top of the compressor by the
outdoor unit PCB.
I.U. expansion valve
opening <300pls
Yes
Is the temperature on the
top of compressor less than esti-
mated condensation temp.?
Check the O.U. expansion valve opening and the
temperature on the top of the compressor by the
outdoor unit PCB.
O.U. expansion valve
opening <70pls
Is the temperature on the
top of compressor less than esti-
mated condensation temp.?
No
No
Yes
Are the connectors for the indoor
expansion valve connected properly?
- Connector on I.U. PCB for ex. valve
- Junction connector for ex. valve
Plug the connectors
properly
No
Yes
Is the outdoor fan normal?
Yes
Yes
Is the refrigerant corectly charged?
Is gas leaking?
Yes
Repair leaks of gas.
Correctly charge refrigerant.
No
Replace fan motor
Charge correct
refrigerant volume
Check the ex valve.
Or remove the cause
of discharge air short-
circuit at indoor and
outdoor units.
No
No
I.U.: Indoor Unit
O.U.: Outdoor Unit
No
No
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......