3 Piping work and
refrigerant charge
SMGB0070 rev.1 - 08/2011
62
Item
(2-10)HP
Maximum piping length (L)
Actual piping length
30
Equivalent piping length
40
Maximum height difference between indoor and
outdoor unit (H)
Outdoor unit higher than indoor unit
30
Indoor unit higher than outdoor unit
20
Refrigerant piping size
Piping connection size of outdoor unit & indoor unit
Outdoor unit
Pipe size
Indoor Unit
Pipe size
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
RAS-2HVRN2
Ø 12.7 (1/2”)(1*)
Ø 6.35 (1/4”)
RWM-2.0FSN3E
Ø 15.88 (5/8”)(1*)
Ø 6.35 (1/4”)
RAS-3HVRNME-AF
Ø 15.88 (5/8”)
Ø 9.53 (3/8”)
RWM-3.0FSN3E
Ø 15.88 (5/8”)
Ø 9.53 (3/8”)
RAS-4H(V)RNME-AF
Ø 15.88 (5/8”)
Ø 9.53 (3/8”)
RWM-4.0FSN3E
Ø 15.88 (5/8”)
Ø 9.53 (3/8”)
RAS-5H(V)RNME-AF
Ø 15.88 (5/8”)
Ø 9.53 (3/8”)
RWM-5.0FSN3E
Ø 15.88 (5/8”)
Ø 9.53 (3/8”)
RAS-6H(V)RNME-AF
Ø 15.88 (5/8”)
Ø 9.53 (3/8”)
RWM-6.0FSN3E
Ø 15.88 (5/8”)
Ø 9.53 (3/8”)
RAS-8HRNME-AF
Ø 25.4 (1”)
Ø 9.53 (3/8”)
RWM-8.0FSN3E
Ø 25.4 (1”)
Ø 9.53 (3/8”)
RAS-10HRNME-AF
Ø 25.4 (1”)
Ø 12.7 (1/2”)
RWM-10.0FSN3E
Ø 25.4 (1”)
Ø 12.7 (1/2”)
N O T E
(1*): 2HP system only (RAS- RWM-2.0FSN3E). If using different piping size for outdoor unit and indoor
unit, a pipe adapter will be required: (Ø12.7 → Ø15.88).
The pipe adapter is factory supplied with the outdoor unit.
Connecting flare adapter (only for RAS-2HVRN2)
No.
Description
1
Liquid line
2
Flare nut (Accessories)
3
Pipe (Accessories)
4
Indoor unit
5
Flare adapter (Accessories)
6
Gas line
7
Pipe (Field supplied)
1
2
3
4
5
6
7
The piping sizes for indoor unit and outdoor unit are different. Attach the flare adapter (accessories) at the indoor piping
union part.
Use the adequate flare adapter as follows:
Indoor unit
Flare adapter
Gas pipe
Liquid pipe
2.0 HP
Big size
(Ø15.88→Ø12.70)
—
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......