5 Control system
SMGB0070 rev. 1 - 08/2011
143
5
Auxiliary electric heater for space heating
All units are delivered with an integrated electric heater for additional heating capacity during cold outdoor temperatures.
The electrical heater also can be used for emergency operation in case of outdoor unit malfunction. The electrical heater
is available for a heating capacity of 3,6 and 9 kW, depending on unit capacity selected.
Electric Heater will only operate if unit is in Space Heating mode. It will always be disabled in any other mode (Hot Sanitary
Water, Swimming Pool and Cooling mode).
Electric Heater will only operate when Heating Accessory is set to Heater or Boiler. In the case of Boiler
it will never operate with both at the same time. The decision as to how to operate will be made considering ambient tem-
perature.
Model
Heater Capacity
Heater steps
Electrical Heater nominal voltage
RWM-2.0FSN3E
3kW
3 steps (1/2/3kW)
1x230V
RWM-3.0FSN3E
3kW
3 steps (1/2/3kW)
1x230V
RWM-4.0FSN3E
6kW
3 steps (2/4/6kW)
1x230V or 3x400V
RWM-5.0FSN3E
6kW
3 steps (2/4/6kW)
1x230V or 3x400V
RWM-6.0FSN3E
6kW
3 steps (2/4/6kW)
1x230V or 3x400V
RWM-8.0FSN3E
9kW
3 steps (3/6/9kW)
3x400V
RWM-10.0FSN3E
9kW
3 steps (3/6/9kW)
3x400V
User Variables:
CODE
REF
Description
Default Value
5-000
HS
Complementary Heating = (Only HP; Heater; Boiler; Boiler)
Only HP
•
Heater bivalent point
Heater will only be enabled when:
Outdoor Ambient Temperature > Electrical heater Bivalent Point (5-006).
20
[
5-006
]
-20
Heat Pump
only
Heat Pump
Heater-SP3
Hea
t De
mand
Heat pump
capacity
Ta (ºC)
Heater-SP2
Heater-SP2
CAP (kW)
Heat pump capacity
Heat pump
only
Heat pump
Heat Demand
Heater-SP3
Heater-SP2
Heater-SP1
-20
20
[
5-006
]
Text (ºC)
User Variable:
CODE
REF
Description
Default Value
Range
Steps
Units
5-006
EHb
Electrical Heater Bivalent Point
0
-20~20
1
ºC
•
Heater step control
Load Factor determines the desired heating supplied by heater. Load factor is calculated by a P+I function ranging from 0
to 100%. Actual heater output will be translated from percentage to a 3-step output using hysteresis system.
Steps
Power
(2/3) HP
(4-6) HP
(8/10) HP
1
1kW
2kW
3kW
2
2kW
4kW
6kW
3
3kW
6kW
9kW
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......