5 Control system
SMGB0070 rev. 1 - 08/2011
138
New water temperature set-point is calculated as follows:
Ttwo
=
Ttwo OTC + Rfact
n
x ( RS - RT)
Where:
Ttwo: Resulting Water Set-Point
Ttwo OTC
n
: Water Set-Point as calculated by OTCn.
Rfact
n
: Room compensation factor (Default 2)
RS: Room set point
RT: Room temperature
Example:
Ttwo OTC
=
-1.3 x Ta + 43.2
Text (outside temperature) =
0ºC
Ttwo OTC =
-1.3x 0 +43.2
=
43.2ºC
RS = 20ºC
RT = 23ºC
RFact
n
= 2 (Default value)
Ttwo =
function (OTC + RFact
n
x (Room set-point – Room temperature)
Ttwo =
function (OTC + 2x (20 – 23)
Ttwo =
43.2 + (-6ºC)
à
Ttwo =
37.2ºC
-06
23ºC (RT)
20ºC (RS)
Outlet temperature set-point ºC
OTC offset x2
Outdoor ambient temperature (ºC)
N O T E
Room set-point factor has no effect on setting fixed temperature operation.
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......