4 Electrical wiring
SMGB0070 rev.1 - 08/2011
77
4
C A U T I O N
• Check to ensure that the indoor pump and the outdoor fan have stopped before electrical wiring work or pe
-
riodical check is performed.
• Protect the wires, drain pipe, electrical parts, from rats or other small animals. If not protected, rats may da
-
mage unprotected parts, and at the worst, a fire will occur.
• Wrap the accessory packing around the wires, and plug the wiring connection hole with the seal material to
protect the product from any condensed water and insects.
• Tightly secure the wires with the cord clamp inside the indoor unit.
• Lead the wires through the knockout hole in the side cover when using conduit.
• Electrical wiring must comply with national and local codes. Contact your local authority in regards to stan
-
dards, rules, regulations, etc.
• Check that the ground wire is securely connected.
N O T E
• Check and test to ensure that if there is more than one source of power supply, that all are turned OFF.
• Be sure to use a dedicated power supply. Never use a power supply shared by another appliance.
4.1.2 Electrical connection of outdoor unit
The correct electrical wiring connection for the outdoor unit is shown below:
1
Using the appropriate cable, connect the power circuit to the appropiate terminals as shown on the wiring label and
the illustration below. In case of RAS-(8/10)HRNME-AF, insert the power source cables L1, L2, L3, and N (for 380-
415V 50Hz), and the earth cable into a ring core (two turns), and fix the cables by using the band (accessory). Do not
insert the cables from a different sides into the ring core.
Wire
Wire
Wire
Wire
2
Connect the power source cables L1 and N (for 230V 50Hz) or L1, L2, L3 to the terminal board, and N (for 400V
50Hz) and the earth conductor to the earthing screw in the electrical box base plate.
RAS-2HVRN2
RAS-(3-6)HVRNME-AF
PCB
Side cover
Power
wires
Transmission
wires
Earth
terminal
Earth terminal
Transmission
wires
Power wires
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......