9 Electrical checks of
the main parts
SMGB0070 rev. 1 - 08/2011
235
9
9.7 Reactor (DCL)
This part is used for changing the alternative current to the direct current for the inverter.
9.7.1 Reactor (DCL) for 1~
RAS-(3-6)HVRNME-AF (230V 50Hz)
Items
Specifications
Character
0.59 mH±15 (at 1 kHz)
Rated current
30 A
DC Resistance
26 mΩ (at 20 °C)
Permissible temperature range
-20ºC to 60ºC
9.7.2 Reactor (DCL) for 3N~
RAS-(4-10)HRNME-AF (400V 50Hz)
Items
Specifications
Character
1.0 mH+10 (at 1 kHz)
Rated current
30 A
Direct resistance
22.8 mΩ+20 (at 20 °C)
Permissible temperature range
-20 ºC to 60 ºC