7 Optional functions
SMGB0070 rev. 1 - 08/2011
204
7.1.3 Pump and valve seizure protection
The pump/valve seizure protection function helps to prevent these components sticking during long periods of inactivity.
Every week the components will run for a short period.
Mixing valves are fully opened and then fully closed (time depends on runtime parameter)
•
Diverting valves are switched on for 1 minute.
•
Pumps are switched on for 1 minute
CODE
Description
Default Value
Range
Steps
Units
8-002
Seizure protection (00:OFF, 01: ON)
OFF
-
-
-
8-010
Operation Day
Mon
Mon~Sun
-
Day
8-011
Start Time (00~24)
01:00
(00~24)
-
Time
7.1.4 DHW anti-legionella protection function
In order to help protect against Legionella in the domestic hot water system, the DHW set-point can be raised to a higher
than normal temperature. The Legionella protection only makes sense if there is a DHW electric heater to raise the DHW
temperature to this high temperature.
N O T E
According to national regulation, the installer must configure this disinfection function field setting
Configuration parameters:
• Operation interval: day(s) of the week at which the domestic water should be heated
• Status: defines whether the disinfection function is turned ON (1) or OFF (0).
•
Start time: time of the day at which the domestic water should be heated
•
Set-point: high water temperature to be reached.
• Interval: time period defining how long the set-point temperature should be maintained.
Anti-Legionella
temperature
set-point
DHW setting
temperature
Time
CODE
Description
Default Value
Range
Steps
Units
8-004
Disinfection function status
Disabled
Disabled / Enabled
-
-
8-003
Operation Interval (Mon~Sun)
Sunday
Daily / Mon ~Sun
-
day
8-005
Start Time (00~24)
01:00
(00~24)
-
Time
8-006
DHW set-point
70
50~70
-
ºC
8-007
Keeping period
10
10~60
-
min
N O T E
• Tariff or DHW timer has no effect.
• When antillegionella function, it is shown in LCD (by ANTL sentence)
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......