12 Troubleshooting
SMGB0070 rev. 1 - 08/2011
343
12
Alarm code
06
Excessively low voltage or excessively high voltage for the inverter
(RAS-(3-6)HVRNME-AF)
• The RUN LED flickers and “ALARM” is displayed on the remote control switch.
•
The unit number, the alarm code and the unit code are alternately displayed on the set temperature section.
The unit number and the alarm code are displayed on the display of the outdoor unit PCB.
-
This alarm code is displayed when the voltage between terminal “P” and “N” of Dip IPM is insufficient and the
alarm has three occurrences in 30 minutes. If the number of occurrences is smaller than two, the retry operation
is performed. The alarm code “06” means fan controller Abnormal Operation.
No
Check the wiring and
the cable capacity
Frequency can increa-
se higher than 60 Hz
Restart the operation
Check the wiring, Dip
IPM and capacitors
(CB1,2) *2).
In case the wiring is co-
rrect, replace Dip IPM
Check capacitors (CB1, 2)
Faulty Dip IPM
Replace it
Replace the capacitors
Connect correctly
Yes
Yes
No
Yes
No
Yes
Compressor stops
immediately
(lower than 20 Hz)
Compressor stops
when frequency
increases (Approx. 20
Hz to 60 Hz)
Faulty Dip IPM.
Replace it
No
No
Yes
Yes
No
Normal
Faulty
Be extremely carefull because of the high voltage
Capacitors have high voltage.
Be extremely carefull *1)
Is the power
supply voltage 230V
±10%?
Is the voltage
over 187V during
operation?
Does the
voltage fall during
the operation because of
the operation of other
apparatus?
Does LED201
on Dip IPM ON after
compressor’s electromag-
netic switches (CMC)
turn ON?
How is
the compres-
sor operation?
Is connection
correctly between
DipIPM and capacitors
(CB1 and CB2), DCL or
CMC?
Is the DC
voltage over 230V?
*1) If the capacitor has a high voltage, perform the high-voltage discharge procedure. Refer to
Procedure of checking
other main parts
.
*2) Checking procedures of the diode module are displayed in item
Procedure of checking other main parts
.
Содержание RWM-(H)FSN3E
Страница 2: ......
Страница 4: ......
Страница 10: ......
Страница 20: ......
Страница 64: ......
Страница 117: ...4 Electrical wiring SMGB0070 rev 1 08 2011 107 4 RWM 8 0 10 FSN3E ...
Страница 118: ...4 Electrical wiring SMGB0070 rev 1 08 2011 108 4 5 2 Electrical wiring diagram for outdoor unit RAS 2HVRN2 ...
Страница 120: ...4 Electrical wiring SMGB0070 rev 1 08 2011 110 RAS 4 6 HVRNME AF ...
Страница 121: ...4 Electrical wiring SMGB0070 rev 1 08 2011 111 4 RAS 4 6 HRNME AF ...
Страница 188: ......
Страница 210: ......
Страница 224: ......
Страница 230: ......
Страница 251: ...10 Spare parts SMGB0070 rev 1 08 2011 241 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 254: ...10 Spare parts SMGB0070 rev 1 08 2011 244 Electrical parts Spare Parts Document EPN 201005 ...
Страница 257: ...10 Spare parts SMGB0070 rev 1 08 2011 247 10 Electrical parts Spare Parts Document EPN 201005 ...
Страница 336: ......
Страница 423: ......